GROUP: |
Mechanical |
TYPE: |
Fire Sprinkler |
SUB-TYPE: |
1 or 2 Family Dwelling |
PRIMARY USE: |
N/A |
WORK DESCRIPTION: |
(1) NEW PRIVATE FIRE HYDRANT AND 6" UNDERGROUND FOR A SINGLE-FAMILY DWELLING. 32' ELEVATION DIFFERENCE BETWEEN NEW 6" FIRE SERVICE DETECTOR CHECK VALVE AND HYDRANT OUTLET. FIRE DEPT REQUIRES 1400 GPM AT 20 PSI AT THE HYDRANT. AVAILABLE MAX PRESSURE: 159 PSI; STATIC MIN: 149; RESIDUAL AT 1400 GPM FLOWING: 132 PSI PER SAR. Revision to approved plans. |
PERMIT ISSUED: |
No |
PERMIT ISSUE DATE: |
N/A |
ISSUING OFFICE: |
N/A |
CURRENT STATUS: |
Application Withdrawn |
CURRENT STATUS DATE: |
07/12/2011 |
|
|
Submitted |
07/12/2011 |
APPLICANT |
Application Withdrawn |
07/12/2011 |
APPLICANT |
|